Product Introduction
Test Report Summary: DIN 4102-1 Fire Behaviour Test for Building Materials
Exposed surface: White
Sample Description: Flame Retardant Coat Fabric
Color: Gray
Composition: Polyester
Test Requested: DIN 4102-1:1998 – Fire Behaviour of Building Materials and Elements, Class B1
Conclusion: The tested sample meets the Class B1 requirements of DIN 4102-1:1998.
Test Details
Sample Description: Flame Retardant Coat Fabric (Gray)
Area Density: 410 g/m²
Sample Size: 190mm x 1000mm & 190mm x 90mm
Conditioning: Samples were conditioned for at least 14 days at 23 ± 2°C and 50 ± 5% relative humidity.
Test Results
1. Brandschacht Test (DIN 4102-15 & 16)
Max. Flame Height: 40 cm
Melting/Burning Through: Yes (Lengthwise and Widthwise)
Burning Droplets: Yes
Average Residual Length: 62.3 cm (Lengthwise), 65.5 cm (Widthwise)
Max. Smoke Temperature: 154.7°C (Lengthwise), 151.8°C (Widthwise)
2. Ignitability Test (DIN 4102-1 Clause 6.2.5)
Fire Application Time: 15 seconds
Flaming Extinguished Before Gauge Mark: Yes (All specimens)
Flaming Reached Measuring Mark (within 20 seconds): No (All specimens)
Max. Flame Height: 7-9 cm
Molten Dripping: No
Smoke Development: Slight
Observations
Residual Length (After Brandschacht Test): Greater than 45 cm for all specimens, meeting Class B1 requirements.
Photo Appendix: SGS authenticated the photo on the original report.